1. Product Introduction:
Split type air conditionerOne to one air conditionerSystem, consisting of one external unit controlling one internal unit
The product is a gateway for controlling split air conditioners. Installed on the signal terminals corresponding to each internal unit.
1.1 Product Overview (divided into two models due to different air conditioning brands)
| AF11 | Can control Midea, Haier, Ge IRACC-AFD Control Daikin Power, Hitachi, Mitsubishi Heavy Industries |
| AFD | Control Daikin |

1.2 Product Basic Specifications and Electrical Parameters
| Product Name | Split type air conditioning intelligent control gateway |
| Applicable brands | Daikin, Toshiba, Hitachi, Mitsubishi Heavy Industries, Mitsubishi Electric, Haier, Midea, Gree, Mitsubishi Heavy Industries Haier, etc. |
| Product model | AFD11 (Daikin only) AF11 (others) |
| Communication interface | RS485, wireless (customized, with built-in wireless module provided) |
| Product size | (mm: length * width * height) 56 * 17.5 |
| Transmission mode | Half duplex |
| Start and stop positions | 1 |
| Data bit/check bit | 8 No NONE |
| power consumption | 40mA-300mA, 2/3W |
| power supply | Self powered 5V (direct power supply to the corresponding terminal of the air conditioning unit) |
| Baud rate | 9600bps |
| Installation Location | Indoor unit of air conditioner |
| Wire requirements | DATA wiring adopts 2-core shielded wire 2 * 1.0 or 2 * 1.5 (cannot be replaced by Ethernet cable) |
2, Installation requirements and wiring diagram
Installation conditions: Installed on indoor units
Maximum limit for internal and external devices: limited to installing one gateway per internal device.
Smart Home Integration Diagram

3. Product Display
The standard product is 485 Wireless product customization, customizable, providing relevant built-in modules.
Terminal and indicator light instructions are shown in the following figure:
3.1 Daikin split unit air duct control gateway—— ModelAFD11

1-3: The indicator lights are described in the following table:
| Indicator light | Name | Function |
| 1 | Wiring terminal | V+V - connected to DC5V internal unit terminal AC1 AC2 connected to HomeBus is the wiring terminal for air conditioning signal line, connected to large internal unit P1P2 |
| 2 | Backup port A2 B2 | Backup 485 interface |
| 3 | 485 interface A1 B1 | Standard 485 interface, commonly used |
4-6: The indicator light is described in the following table:
| Indicator light | is turned off | Flashing | Always on | Flashing again |
| 4 | - Backup | - Backup | - Backup | - Backup |
| 5 | Equipment abnormality | Search for | in air conditioner, search completed | Air conditioner controlled |
| 6 | Communication abnormality | 485 communication | not working | Communication between central control host and gateway |
3.2(non Daikin) split unit air duct control gateway - modelAF11

1-3: Indicator lights are described in the following table:
| Indicator lights | Name | Function |
| 1 | Wiring terminals | is directly connected to the air conditioning signal terminal, and the terminals of different brands of air conditioners are different, as shown in the table below |
| 2 | Backup port A2 B2 | Backup 485 interface |
| 3 | 485 interface A1 B1 | Standard 485 interface, commonly used |
4-6: Indicator light instructions are shown in the table below:
| Indicator light | is off | flashes | is always on | flashes again |
| 4 | - Backup | - Backup | - Backup | - Backup |
| 5 | Equipment abnormality | Search in air conditioner | Search completed | Air conditioner controlled |
| 6 | Communication abnormality | 485 communication | Not working | Communication between central control host and gateway |
4. Ports corresponding to gateway and air conditioner internal unit
One to one split air conditioner internal unit and gateway docking ports are as follows (connection cable is standard for the product): Midea internal unit: five pin red socket
Haier internal unit: four pin red socket
| controllableAir conditioner brand | model | gatewayport | air conditionerport | wiring | gatewaypower supply | RS485A1 B1 Mouth |
| Daikin | IRACC-AFD11 | AC1 AC2 | P1 P2 | Standard | Wiring Self powering | Connected to Smart Host |
| Toshiba | IRACC-AF11 | AC | A B | Standard | Wiring Self Powered | Connected to Smart Host |
| Hitachi | IRACC-AF11 | AC | A B/CN2 | Standard | Wiring Self Powered | Connected to Smart Host |
| Hisense | IRACC-AF11 | AC | A B/WIRED | Standard | Wiring Self Powered | Connected to Smart Host |
| Midea | IRACC-AF11 | AC | CN40 | Standard | Wiring Self Powered | Connected to Smart Host |
| Gree | IRACC-AF11 | AC | com3/wifi/com bms | Standard | Wiring Self Powered | Connected to Smart Host |
| Haier | IRACC-AF11 | AC | WIFI | Standard | Wiring Self Powered | Connected to Smart Host |
| Mitsubishi Electric | IRACC-AF11 | AC | CN105 | Standard | Wiring Self Powered | Connected to Smart Host |
| Mitsubishi Heavy Industries | IRACC-AF11 | AC | X Y | Standard | Wiring Self Powered | Connected to Smart Host |
| Mitsubishi Heavy Industries Haier | IRACC-AF11 | AC | X Y | Standard | Wiring Self Powered | Connected to Intelligent Host |
5. Installation and Wiring Diagram (Taking Haier One to One Duct Fan as an Example)

6. Power on Test:
(1)Power on: After the gateway is connected to the internal unit, it supplies power to itself, and the signal light "5" lights up
(2) The 485 communication line is connected to the intelligent central control, and the signal light "6" lights up after communication
(3) If the central control host can monitor and control the air conditioning internal unit normally, the debugging is completed.
7. Gateway Address Dialing Method (Register Address),Gateway AssistanceAddress default "01 ”IRACC module dialing instance (code position 1-2-3-4-5-6)
1st slave dialing 000010:

2nd slave dialing 000100:

3rd slave dialing 000110:

IRACC Split machine gateway dialing address table:" 1 "indicates dialing up to ON
| address | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
| dialing | 000010 | 000100 | 000110 | 001000 | 001010 | 001100 | 001110 | 010000 |
| address | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 |
| dialing | 010010 | 010100 | 010110 | 011000 | 011010 | 011100 | 011110 | 100000 |
| address | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 |
| DIP switch | 100010 | 100100 | 100110 | 101000 | 101010 | 101100 | 101110 | 110000 |
| Address | 25 | 26 | 27 | 28 | 29 | 30 | 31 | 32 |
| DIP switch | 110010 | 110100 | 110110 | 111000 | 111010 | 111100 | 111110 | 000001 |
| Address | 33 | 34 | 35 | 36 | 37 | 38 | 39 | 40 |
| DIP switch | 000011 | 000101 | 000111 | 001001 | 001011 | 001101 | 001111 | 010001 |
| Address | 41 | 42 | 43 | 44 | 45 | 46 | 47 | 48 |
| DIP switch | 010011 | 010101 | 010111 | 011001 | 011011 | 011101 | 011111 | 100001 |
| Address | 49 | 50 | 51 | 52 | 53 | 54 | 55 | 56 |
| DIP switch | 100011 | 100101 | 100111 | 101001 | 101011 | 101101 | 101111 | 110001 |
| Address | 57 | 58 | 59 | 60 | 61 | 62 | 63 | host |
| DIP switch | 110011 | 110101 | 110111 | 111001 | 111011 | 111101 | 111111 | 000000 |
Modbus protocol
Monitoring
Operation/stop status of indoor unit
Operating modes: cooling, heating, air supply, dehumidification (depending on the performance of the indoor unit), set temperature
Set temperature of indoor unit
Indoor temperature, suction temperature of indoor unit
Airflow LL, · L, · M, · H, · HH - (depending on the performance of the indoor unit)
Forced stop status: Abnormal fault and warning codes for the forced stop of indoor units
control
Operation/Stop Control Indoor Unit Operation/Stop
Operating modes: cooling, heating, air supply, dehumidification (depending on the performance of the indoor unit), set temperature, and set temperature for cooling/heating
Airflow LL, · L, · M, · H, · HH - (depending on the performance of the indoor unit)
retrieve
System information communication status
How many indoor units are connected, and what is the network address of each indoor unit
Modbus communication parameters of gateway
485 communication parameters
Baud rate 9600bps Data bits 8 Stop bits 1 Parity check bits NONE
Function code:
This gateway supports the following functional codes. If this gateway receives a function code outside of this table, the function code will be considered illegal and this gateway will provide an abnormal response. Function code information broadcast
0x04 (04) Read Input Register
0x06 (06) Preset Single Register
0x10 (16) Preset Multiple Register
Function Format:
Read Input Register (0x04)
- [Function]
Read the value from the input register.
Please refer to "3. Modbus Register" for its address and input register content. - [Search]
The query information lists the starting address of the register and the number of registers.
The starting address of register addressing is 0: the address of register 30001 is 0x0000.
This function can read up to 4 VRV indoor unit information in one query.
Preset single register (0x06)
- [Function]
Write a value to the hold register. In the case of broadcasting, this value is written into the hold register. Its address
Please refer to "3. Modbus Register" for the contents of the register.
- [Search]
The query information lists the starting address and a value of the register.
The address starting from 40001 in register addressing is 0x0000.
Preset multiple registers (0x10)
- [Function]
Write multiple values to the hold register. In the case of broadcasting, this value is written to the same for all slaves
The type is kept in the register. Please refer to "3. Modbus Register" for its address and local parameters in the hold register.
- [Search]
The query information lists the starting address, data size, and multiple values of the register. Register addressing starting address is 0:
The address of register 40001 is 0x0000. This function can write up to 1 VRV indoor in one query
Machine information.
Modbus Register
4.1 0x04 (04) Read Input Register (Input Register 3-1.)
4.2 Adapter Status Address
| Indoor unit connection status address | Content |
|---|---|
| 30001 | Indoor unit connection status address |
| 30002 | Indoor unit connection status (1-00~1-15) |
| 30003 | Indoor unit connection status (2-00~2-15) |
| 30004 | Indoor unit connection status (3-00~3-15) |
| 30005 | Indoor unit connection status (4-00~4-15) |
Example of adapter status:
Query 01 04 00 00 01 31 CA
Response 01 04 02 00 01 78 F0
Among them, query 01 04 00 00 01 31 CA
01 Slave Address 01~15
04 Function Code 04 Query
The address of register 30001 is 0x0000
00 01 Query 1 register
31 CA verification CRC16
Response 01 04 02 00 01 78 F0
01 Slave Address 01~15
04 Function Code 04 Query
02 Length
01 Adapter status 00: Not ready; 01: Get ready
78 F0 verification CRC16
Change the slave address as shown in Attachment 2
4.3 Indoor unit connection status:
Query 01 04 00 01 00 04 A0 09
Response 01 04 08 FF FF 3F FF 00 00 58 28
04 Function Code 04 Query
| 00 | 01 | The address of register 30002 is 0x0001 |
|---|---|---|
| 00 | 04 | Query 4 registers |
| A0 | 09 | Verify CRC16 |
Response: 01 04 08 FF FF 3F FF 00 00 58 28
| 01 | slave address | 01~15 |
|---|---|---|
| 04 | Function code | 04 Query |
| 08 | Length | |
| FF | FF 3F | 3F FF 00 There are a total of 64 air conditioning units. 0: Not connected; 1: Connect |
58 28 Verify CRC16
4.4 Status information of indoor unit
4.4.1 Adapter address According to the image content you provided, the following is the complete address mapping table for querying indoor unit status information:
Address mapping table for querying indoor unit status information
| Address range | Address range for indoor unit | Address Range | Indoor unit address |
|---|---|---|---|
| 32001-32006 | 1-00 | 32193-32198 | 3-00 |
| 32007-32012 | 1-01 | 32199-32204 | 3-01 |
| 32013-32018 | 1-02 | 32205-32210 | 3-02 |
| 32019-32024 | 1-03 | 32211-32216 | 3-03 |
| 32025-32030 | 1-04 | 32217-32222 | 3-04 |
| 32031-32036 | 1-05 | 32223-32228 | 3-05 |
| 32037-32042 | 1-06 | 32229-32234 | 3-06 |
| 32043-32048 | 1-07 | 32235-32240 | 3-07 |
| 32049-32054 | 1-08 | 32241-32246 | 3-08 |
| 32055-32060 | 1-09 | 32247-32252 | 3-09 |
| 32061-32066 | 1-10 | 32253-32258 | 3-10 |
| 32067-32072 | 1-11 | 32259-32264 | 3-11 |
| 32073-32078 | 1-12 | 32265-32270 | 3-12 |
| 32079-32084 | 1-13 | 32271-32276 | 3-13 |
| 32085-32090 | 1-14 | 32277-32282 | 3-14 |
| 32091-32096 | 1-15 | 32283-32288 | 3-15 |
| 32097-32102 | 2-00 | 32289-32294 | 4-00 |
| 32103-32108 | 2-01 | 32295-32300 | 4-01 |
| 32109-32114 | 2-02 | 32301-32306 | 4-02 |
| 32115-32120 | 2-03 | 32307-32312 | 4-03 |
| 32121-32126 | 2-04 | 32313-32318 | 4-04 |
| 32127-32132 | 2-05 | 32319-32324 | 4-05 |
| 32133-32138 | 2-06 | 32325-32330 | 4-06 |
| 32139-32144 | 2-07 | 32331-32336 | 4-07 |
| 32145-32150 | 2-08 | 32337-32342 | 4-08 |
| 32151-32156 | 2-09 | 32343-32348 | 4-09 |
| 32157-32162 | 2-10 | 32349-32354 | 4-10 |
| 32163-32168 | 2-11 | 32355-32360 | 4-11 |
| 32169-32174 | 2-12 | 32361-32366 | 4-12 |
| 32175-32180 | 2-13 | 32367-32372 | 4-13 |
| 32181-32186 | 2-14 | 32373-32378 | 4-14 |
| 32187-32192 | 2-15 | 32379-32384 | 4-15 |
Instructions:
- Each indoor unit occupies 6 consecutive register addresses
- The address format is "group number serial number", for example, "1-00" represents the indoor unit number 00 of the first group
- Supports a total of 4 groups, each consisting of 16 indoor units, with a maximum support of 64 indoor units
- Use function code 0x04 to read these registers and obtain indoor unit status information
This table is used to query the operating status of indoor units, including switch status, wind speed, operating mode, set temperature, indoor temperature, fault codes, and other information.
4.4.2 Querying the status of indoor units:
Querying 01 04 07 D0 00 06 70 85
Responding 01 04 0C 50 00 42 02 01 18 00 01 0A 80 00 F6 FA
Among them, querying: 01 04 07 D0 00 06 70 85
01 Slave address 01~15
04 Function Code 04 Query
The address of the 07 D0 register 32001 is 0x07d0
00 06 Query 6 registers
70 85 verification CRC16
Six registers store the status of a hollow indoor unit.
Register 32001 (the starting address of the first indoor unit in the cavity is 0x07d0,
Register 32007 (the starting address of the second indoor unit in the cavity is 0x07d6,
Register 32013 (the starting address of the third indoor unit in the cavity is 0x07dc,
………
Response: 01 04 0C 50 00 42 02 01 18 00 00 01 0A 80 00 F6 FA
01 Slave Address 01~15
04 Function Code 04 Query
0C length
50 air volume/wind direction hh air volume=0x50&0xf0 10=1, 20=II, 30=m, 40=h, 50=hh, A0=automatic
swaying wind
This register BIT2-BIT0 bits are for wind direction 0-1-2-3-4-4-5-6-7 (0-horizontal direction, 4 vertical direction, 5 reserved for 6, 7 swing wind)
This register BIT3 indicates the automatic wind direction status of the indoor unit (0-OFF with no wind direction, 1-ON with wind direction)
00 switch off switch=0x00&0x01 1 1=On 0=Off 42 Filter cleaning flag
02 cooling mode=0x02&0x0f0=supply air, 1=heating, 2=cooling, 7=dehumidification
01 18 set temperature 28 set temperature=(0x01100+0x18)/10; 00 fault code attached 01 0A indoor temperature 26.6 indoor temperature=(0x01)100+0x0a)/10;
08 00 Temperature sensor status 0x0800 Normal 0x0001 Abnormal F6 FA verification CRC16
Querying the status of indoor units can be done by querying a single register or by querying multiple registers together.
| Example | 01 | 04 | 07 | D0 | 00 | 01 | 31 | 47 | Query indoor unit | 1's switch and air volume |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 04 | 07 | D7 | 00 | 01 | 80 | 86 | Query indoor unit | Mode 2 | |
| 01 | 04 | 07 | D6 | 00 | 0C | 10 | 83 | Query indoor unit | Status of indoor units 2 and 3 |
4.5 0x06 (06) Preset Single Register
4.5.1. Adapter address
Address Content 40001 DIII Network Address
| Address | Indoor unit address | Address | Indoor unit address |
|---|---|---|---|
| 42001-42003 | 1-00 | 42097-42099 | 3-00 |
| 42004-42006 | 1-01 | 42100-42102 | 3-01 |
| 42007-42009 | 1-02 | 42103-42105 | 3-02 |
| 42010-42012 | 1-03 | 42106-42108 | 3-03 |
| 42013-42015 | 1-04 | 42109-42111 | 3-04 |
| 42016-42018 | 1-05 | 42112-42114 | 3-05 |
| 42019-42021 | 1-06 | 42115-42117 | 3-06 |
| 42022-42024 | 1-07 | 42118-42120 | 3-07 |
| 42025-42027 | 1-08 | 42121-42123 | 3-08 |
| 42028-42030 | 1-09 | 42124-42126 | 3-09 |
| 42031-42033 | 1-10 | 42127-42129 | 3-10 |
| 42034-42036 | 1-11 | 42130-42132 | 3-11 |
| 42037-42039 | 1-12 | 42133-42135 | 3-12 |
| 42040-42042 | 1-13 | 42136-42138 | 3-13 |
| 42043-42045 | 1-14 | 42139-42141 | 3-14 |
| 42046-42048 | 1-15 | 42142-42144 | 3-15 |
| 42049-42051 | 2-00 | 42145-42147 | 4-00 |
| 42052-42054 | 2-01 | 42148-42150 | 4-01 |
| 42055-42057 | 2-02 | 42151-42153 | 4-02 |
| 42058-42060 | 2-03 | 42154-42156 | 4-03 |
| 42061-42063 | 2-04 | 42157-42159 | 4-04 |
| 42064-42066 | 2-05 | 42160-42162 | 4-05 |
| 42067-42069 | 2-06 | 42163-42165 | 4-06 |
| 42070-42072 | 2-07 | 42166-42168 | 4-07 |
| 42073-42075 | 2-08 | 42169-42171 | 4-08 |
| 42076-42078 | 2-09 | 42172-42174 | 4-09 |
| 42079-42081 | 2-10 | 42175-42177 | 4-10 |
| 42082-42084 | 2-11 | 42178-42180 | 4-11 |
| 42085-42087 | 2-12 | 42181-42183 | 4-12 |
| 42088-42090 | 2-13 | 42184-42186 | 4-13 |
| 42091-42093 | 2-14 | 42187-42189 | 4-14 |
|---|---|---|---|
| 42094-42096 | 2-15 | 42190-42192 | 4-15 |
| Group control address | 42193-42195 | 5-00 |
4.6 Control indoor unit:
4.6.1 Switch and Wind Speed Setting
Control 01 06 07 D0 10 60 84 AF
Response 01 06 07 D0 10 60 84 AF
Control example: 01 06 07 D0 10 60 84 AF
01 Slave Address 01~15
06 Function Code 06 Control
The address of register 42001 in 07D0 is 0x0740
10 (BIT7-BIT4) 10 wind speed 120 wind speed 130 wind speed m 40 wind speed h 50 wind speed hh A0=automatic
(BIT2-BIT0) (0-1-2-3-4-5-6-7) (0-horizontal direction, 4 vertical directions, 5 reserved, 7 swing wind)
60 shutdown 61 startup
Special reminder: FF 60 means no air volume control operation, only shutdown
FF 61 means no air volume control operation, only power on
20 FF air volume 1 without power on/off operation
50 FF air volume hh without power on/off operation
84 AF verification CRC16
4.6.2 Mode Setting
Control 01 06 07 D4 00 02 49 47
Response 01 06 07 D4 00 02 49 47
Control example: 01 06 07 D0 10 60 84 AF
00 A0 16 degrees Celsius
0B 52 Verify CRC16
01 Slave Address
| 07 | D0 | Register 42005 | The address is 0x0744 |
|---|---|---|---|
| 00 | 02 | cooling mode | |
| 00 | 00 | Ventilation mode, 00 | 01 Heating mode, |
| 00 | 02 | Cooling mode, 00 | 07 Dehumidification mode |
| 00 | 03 | Auto Mode |
| 49 | 47 | Verify CRC16 |
|---|
4.6.3 Temperature Setting
Control 01 06 07 D2 00 A0 28 FF
Response 01 06 07 D2 00 A0 28 FF
Control example: 01 06 07 D2 00 A0 28 FF
01 Slave Address 01~15
06 Function Code 06 Control
07 D2 寄存器 42003 的地址是 0x07d2
00 A0 00 A0 16 摄氏度,00 AA 17 摄氏度,………
28 FF 校验 CRC16Three registers store control information for an indoor air conditioning unit,
Register 42001 (the starting address of the first indoor unit of the air conditioner is 0x07d0,
Register 42004 (the starting address of the indoor unit of the second air conditioner is 0x07d3,
Register 42007 (the starting address of the third indoor unit of the air conditioner is 0x07d6,
4.7 0x10 (16) Preset: Multiple registers
Control indoor unit:
Control 01 10 07 D9 00 03 06 10 60 00 02 00 A0 0B 52
Response 01 10 07 D9 00 03 50 87
Control example: 01 10 07 D9 00 03 06 10 60 00 02 00 A0 C2 A5
01 Slave Address 01~15
10 Function Code 10 Control
07 D9 寄存器 42010 的地址是 0x07d9(第 4 台空调室内机)
00 03 预置 3 个寄存器
06 数据大小(bytes)
10 60 10 风速 11 60 关机
00 02 制冷模式Response: 01 10 07 D9 00 03 50 87
01 Slave Address 01~15
10 Function Code 10 Control
07 D9 寄存器 42010 的地址是 0x07d9(第 4 台空调室内机)00 03 Preset 3 registers
50 87 Verify CRC16
Preset multiple registers only support writing all control parameters to a single indoor unit at once!
4.8 Query Setting Air Conditioning Type
0X05 Query/Set Air Conditioning Model
Query: 01 05 00 00 CD CA
01 Slave Address
05 Function Code
00 00 Register Address Default 00 00
00 00 00 Fill Byte Default 00 00
CD CA Check CRC16
Return: 01 05 00 00 01 00 CC 5A
00 Slave Address
05 Function Code
00 00 Register Address Default 00 00
00 00 Air Conditioning Type. Please refer to the table below for details:
CC 5A Verify CRC16
Settings: 01 05 00 01 00 9D DA
01 Slave Address
05 Function Code
00 01 Register Address
01 00 Air Conditioning Type 01 00 Represents Daikin
9D DA Verify CRC16
Return: 01 05 00 01 00 9D DA
00 Slave Address
05 Function Code
00 01 Register Address
01 00 Air Conditioning Type. Please refer to the following table for details:
9D DA verification CRC16
5. Fresh air: both reading and control are 00
Attachment 1
Daikin exception code mapping table:
| Value 2 | Code | Value 1 | Code |
|---|---|---|---|
| 0 | 0 | 0 | 0 |
| 1 | A | 1 | 1 |
| 2 | C | 2 | 2 |
| 3 | E | 3 | 3 |
| 4 | H | 4 | 4 |
| 5 | F | 5 | 5 |
| 6 | J | 6 | 6 |
| 7 | L | 7 | 7 |
| 8 | P | 8 | 8 |
| 9 | U | 9 | 9 |
| 10 | 9 | 10 | A |
| 11 | 8 | 11 | H |
| 12 | 7 | 12 | C |
| 13 | 6 | 13 | J |
| 14 | 5 | 14 | E |
| 15 | 4 | 15 | F |
| 16 | 3 | ||
| 17 | 2 | ||
| 18 | 1 | ||
| 19 | G | ||
| 20 | K | ||
| 21 | M | ||
| 22 | N | ||
| 23 | R | ||
| 24 | T | ||
| 25 | V | ||
| 26 | W | ||
| 27 | X | ||
| 28 | Y | ||
| 29 | Z | ||
| 30 | * | ||
| 31 |
For example: Value 1=4 Value 2=9 Exception code=U4
Attachment 2
| Code | Fault Description | Code | Fault Description |
|---|---|---|---|
| 01 | Action of indoor unit protection device | 31 | Abnormal combination of indoor and outdoor unit capacity |
| 02 | Action of outdoor unit protection device (outdoor unit fan protection tripped) | 32 | Normal internal machine disconnection |
| 03 | communication failure | 35 | The external or internal machine numbers are duplicated, and the internal and external machine models do not match |
| 04 | Communication between external motherboard and frequency converter board | 36 | |
| Communication between the external motherboard and the fan frequency conversion board | |||
| 05 | Power phase sequence | 38 | Outdoor unit protection circuit action |
| 06 | Power module undervoltage (indoor unit voltage too low, commercial split), fan control module voltage abnormal | 39 | Constant speed compressor overcurrent or zero current |
| 07 | Low exhaust superheat | 3a | Outdoor unit capacity error |
| 08 | High temperature at the top of the compressor | 3b | The combination of outdoor unit and sub unit is incorrect, and the power setting is incorrect |
| 09 | Outdoor fan with built-in temperature sensor detects high temperature | 3d | Communication abnormality between outdoor unit host and sub unit |
| 0A | Abnormal communication between outdoor unit modules | 41 | Refrigeration overload protection |
| 0b | Outdoor unit submodule setting error | 42 | Heating overload protection |
| 0c | Outdoor unit main module setting error | 43 | Low pressure ratio |
| 0d | Abnormal water temperature (water heat source) | 44 | Low voltage too high |
| 11Ti | Temperature sensor open circuit or short circuit | 45 | High exhaust pressure |
| 12To | Temperature sensor open circuit or short circuit | 46 | Low exhaust pressure |
| 13Tl | Temperature sensor open circuit or short circuit | 47 | Low pressure, low pressure |
| 14Tg | Temperature sensor open circuit or short circuit | 48 | Inverter overcurrent protection action |
| 15Ta | Abnormal ambient temperature sensor (total heat exchanger) | 51 | Compressor inverter detects zero current |
| 16 | New air remote transmission temperature sensor open circuit or short circuit | 52 | Compressor inverter detects overcurrent |
| 17 | Line controller built-in sensor abnormal | 53 | Compressor inverter detects abnormality |
| 18 | Indoor fan motor temperature sensor abnormal | 54 | Compressor inverter temperature sensing overheating |
| 19 | Action of indoor fan motor protection device | 55 | Inverter not working |
| 20 | Abnormal temperature sensing at the top of the compressor | 56 | Abnormal fan position detection |
| 21 | Abnormal high voltage sensor | 57 | Fan control substrate protection action |
| 22 | Abnormal external air temperature sensing | 58 | Fan control abnormal |
| 23 | Abnormal temperature sensing at the top of the compressor | 59 | Abnormal current of the outdoor unit fan chopper |
| 24 | Abnormal temperature sensing of the cooler | 5a | Fan control substrate temperature rise protection |
| 25 | Abnormal Temperature Sensing of Cooler | 5b | Fan Control Board Overcurrent Protection |
| 29 | Abnormal Low Voltage Sensor | 5c | Abnormal Current Sensor of Fan Control Board |
| 2A | Abnormal Water Temperature Sensor (Water and Heat Source) | 96 KPI | Abnormal Room Temperature Sensor (FSN) |
|---|---|---|---|
| 30 | Wiring Error (FSN) CH Device Connection Error (FSXNQ) | 97 KPI | Outdoor temperature sensor abnormal (FSN) |
| EE | Compressor protection |
Attachment 3
Table: Type code correspondence table
| Air conditioning type | Type code |
|---|---|
| Daikin | 01 00 |
| Toshiba | 02 00 |
| Mitsubishi Heavy Industries | 03 00 |
| mitsubishi heavy-haier | 04 00 |
| Mitsubishi Electric | 05 00 |
| Hitachi | 06 00 |
| Hisense Hitachi | 07 00 |
| Panasonic | 08 00 |
| Haier | 09 00 |
| York | 0A 00 |
| Bosch | 0B 00 |
| Midea | 0C 00 |
| Gree | 0D 00 |
| Carrier | 0E 00 |
| Samsung | 0F 00 |
| LG | 10 00 |
The default factory address for slave devices is 01
Change the method to send 01 06 AA * * CRC16 device to the gateway. If the reply is consistent with the sending, it is considered successful
Example: 01 06 AA 03 DF 78
Change the slave address to 03
Leave a Reply