Midea Home Multi split Air Conditioner Modbus Centralized Control Communication Protocol

freeFree Technical Resource

This content is free to read, suitable for basic learning and search traffic.

Midea Home Multi split Air Conditioner Modbus Centralized Control Communication Protocol缩略图
Midea Home Multi split Air Conditioner Modbus Centralized Control Communication Protocol插图

1.Communication rules

0x02

n*128+30000+10

Remark

data bit: 8Bits

parity bit: None

stop bit: 1Bits

2. Command function code

function codeFunction NameFunction
0x02Read Discrete input
Read discrete quantities
Read
0x04Read Input Register
Read input register
Read
0x06Write Single Register
Write a single register
Write

3. Abnormal reply

The master device sends a request and waits for a response from the slave device. When no errors occur, Reply normally from the device, If the data verification is incorrect, If the device does not reply. When the data sent by the main device is incorrect (Except for inspection errors) , Reply with abnormal code from the device.

CodeNamemeaning
0x01Illegal function codeThe received function code is not supported by the slave
0x02Illegal data addressThe received data address is not supported by the slave
0x03Illegal dataThe received data value is not supported by the slave

4. ModbusData frame description

Device addressfunction codedataCRCVerification
1byte1byteNbyte2byte

4.1

0x02Read discrete input

Example: Assuming that the address of the discrete quantity register in Unit 2 is read as10257~10259the data;

Starting address=Register address-10001=10257-10001=256, namely0x0100

2Number in machine10257~10259The actual address is0~2, The number of discrete inputs is3

Request message: 00 02 01 00 00 03 38 26

response message: 00 02 01 05 60 77

Request messageresponse message
domain name (hexadecimal) domain name (hexadecimal)
Device address00Device address00
function code02function code02
Starting address high byte01byte count01
Low byte starting address00input state7-005
Discrete input quantity high byte00Low bit of verification code60
Discrete input quantity low byte03High bit of verification code77
Low byte checksum38  
High byte checksum26  

What is the input status byte in the reply message05, The corresponding binary is00000101, 0~2The data for the address are as follows:101.View Address Mapping Table, Power on1, Fault status0, Online status1.

4.2

0x04Read input register

Example: Read the input register address of internal machine 0 as30001~30013

Starting address=Register address-30001=30001-30001=0, namely0x00

0Number in machine30001~30013The actual address is0~12,The number of input registers is13

Request message: 00 04 00 00 00 0D 30 1E

response message: 00 04 1A 00 01 00 00 00 00 00 54 00 64 00 1E FF FF 00 6B 00 6E 00 00 00 00 00 00 00 00 0B D7

Request messageresponse message
domain name (hexadecimal) domain name (hexadecimal)
Device address00Device address00
function code04function code04
Starting address high byte00byte count1A
Low byte starting address00Input register 1 high byte00
Input register quantity high byte00Input register 1 low byte01
Low byte input register quantity0DInput register 2 high byte00
Low byte checksum30Input register 2 low byte00
High byte checksum1EInput register 3 high bytes00
  Input register 3 low byte00
  Input register 4 high bytes00
  Input register 4 low byte54
  Input register 5 high bytes00
  Input register 5 low byte64
  Input register 6 high bytes00
  Input register 6 low byte1E
  Input register 7 high bytesFF
  Input register 7 low byteFF
  Input register 8 high bytes00
  Input register 8 low byte6B
  Input register 9 high byte00
  Input register 9 low byte6E
  input register10high byte00
  input register10low-order byte00
  input register11high byte00
  input register11low-order byte00
  input register12high byte00
  input register12low-order byte00
  input register13high byte00
  input register13low-order byte00
  Low byte checksum0B
  High byte checksumD7

Query the number of input registers as13 (0x0D) , Therefore, the number of bytes in the response message is26 (0x1A) (The value of an input register consists of two bytes) , The specific meaning of the input register values can be viewed in the address mapping table.

4.3

0x06Write a single register

Example: What is the register address for controlling the power on/off of Unit 040001, The startup parameters are1

Starting address=Register address-40001=40001-40001=0, namely0x00

The register setting parameter is1, Power on

Request message: 00 06 00 00 00 01 49 DB

response message: 00 06 00 00 00 01 49 DB

Request messageresponse message
domain name (hexadecimal) domain name (hexadecimal)
Device address00Device address00
function code06function code06
Register address high byte00Output address high byte00
Low byte register address00Output address low byte00
Register value high byte00Output value high byte00
Register value low byte01Output value low byte01
Low byte checksum49Low byte checksum49
High byte checksumDBHigh byte checksumDB

Another example: What is the register address for controlling the hot mode of mechanism 040002, The heating parameters are02

Starting address=Register address-40001=40002-40001=1, namely0x01

Register setting parameters02, heating

Request message: 00 06 00 01 00 02 58 1A

response message: 00 06 00 01 00 02 58 1A

Request messageresponse message
domain name (hexadecimal) domain name (hexadecimal)
Device address00Device address00
function code06function code06
Register address high byte00Output address high byte00
Low byte register address01Output address low byte01
Register value high byte00Output value high byte00
Register value low byte02Output value low byte02
Low byte checksum58Low byte checksum58
High byte checksum1AHigh byte checksum1A

5. Internal and External Machine Variable Mapping Table

  Communication rules
communication method: MODBUS
Baud rate:  9600Bps   
start position: 1Bit
data bit: 8Bits
parity bit: None
stop bit: 1Bit
ModbusData frame description
Device addressfunction codedataCRCVerification
1byte1byteNbyte2byte
Command function code
function codeFunction NameFunction
0x02Read Discrete input
Read discrete quantities
Read
0x04Read Input Register
Read input register
Read
0x06Write Single Register
Write a single register
Write
0x02Read discrete input0x04Read input register0x06Write a single register
hostSlavehostSlavehostSlave
Request messageresponse messageRequest messageresponse messageRequest messageresponse message
Device addressDevice addressDevice addressDevice addressDevice addressDevice address
function codefunction codefunction codefunction codefunction codefunction code
Starting address high bytebyte countStarting address high bytebyte countNRegister address high byteOutput address high byte
Low byte starting addressinput state7-0Low byte starting addressInput register 1 high byteLow byte register addressOutput address low byte
Discrete input quantity high byteCRC16Low bit of verification codeInput register quantity high byteInput register 1 low byteRegister value high byteOutput value high byte
Discrete input quantity low byteCRC16High bit of verification codeLow byte input register quantityInput register 2 high byteRegister value low byteOutput value low byte
CRC16Low byte checksumCRC16Low byte checksumInput register 2 low byteCRC16Low byte checksumCRC16Low byte checksum
CRC16High byte checksumCRC16High byte checksumInput register 3 high bytesCRC16High byte checksumCRC16High byte checksum
Input register 3 low byte
---------------
input registerN/2high byte
input registerN/2low-order byte
CRC16Low byte checksum
CRC16High byte checksum
(note: N=Input the number of registers*2)
Abnormal replyReply from the machine in case of abnormality
CodeNamemeaningDevice address
0x01Illegal function codeThe received function code is not supported by the slavefunction code|FUNC_ERROR (128)
0x02Illegal data addressThe received data address is not supported by the slaveAbnormal reply code
0x03Illegal dataThe received data value is not supported by the slaveCRC16Low byte checksum
CRC16High byte checksum
The master device sends a request and waits for a response from the slave device. When no errors occur,
Reply normally from the device, If the data verification is incorrect, If the device does not reply.
When the data sent by the main device is incorrect (function code, data address, Data is invalid) , Reply with abnormal code from the device.
Command typeInternal addressregister addressvariable namedata lengthmeaning
Read discrete quantities
0x02
0Number in machine10001Power on1bit0:Shutdown; 1: Power on
10002Fault1bit0:fault-free; 1: Faulty
10003Online status1bit0:offline; 1: online
100041bitreserve
100051bitreserve
100061bitreserve
100071bitreserve
100081bitreserve
10009-10128reserve
1Number in machine10129Power on1bit0:Shutdown; 1: Power on
10130Fault1bit0:fault-free; 1: Faulty
10131Online status1bit0:offline; 1: online
101321bitreserve
101331bitreserve
101341bitreserve
101351bitreserve
101361bitreserve
10137-10256reserve
nNumber in machinen*128+10000+1Power on1bit0:Shutdown; 1: Power on
n*128+10000+2Fault1bit0:fault-free; 1: Faulty
n*128+10000+3Online status1bit0:offline; 1: online
n*128+10000+41bitreserve
n*128+10000+51bitreserve
n*128+10000+61bitreserve
n*128+10000+71bitreserve
n*128+10000+81bitreserve
n*128+10000+9--n*128+10000+128reserve
63Number in machine18065Power on1bit0:Shutdown; 1: Power on
18066Fault1bit0:fault-free; 1: Faulty
18067Online status1bit0:offline; 1: online
180681bitreserve
180691bitreserve
180701bitreserve
180711bitreserve
180721bitreserve
18073-18192reserve
Read discrete quantities
0x02
(note: Currently, only Unit 0 is open for external use)
0Extra phone18193Power on1bit0:Shutdown; 1: Power on
18194Fault1bit0:fault-free; 1: Faulty
18195Online status1bit0:offline; 1: online
181961bitreserve
181971bitreserve
181981bitreserve
181991bitreserve
182001bitreserve
18201-18320reserve
1Extra phone18321Power on1bit0:Shutdown; 1: Power on
18322Fault1bit0:fault-free; 1: Faulty
18323Online status1bit0:offline; 1: online
183241bitreserve
183251bitreserve
183261bitreserve
183271bitreserve
183281bitreserve
18329-18448reserve
nExtra phonen*128+18192+1Power on1bit0:Shutdown; 1: Power on
n*128+18192+2Fault1bit0:fault-free; 1: Faulty
n*128+18192+3Online status1bit0:offline; 1: online
n*128+18192+41bitreserve
n*128+18192+51bitreserve
n*128+18192+61bitreserve
n*128+18192+71bitreserve
n*128+18192+81bitreserve
n*128+18192+9--n*128+18192+128reserve
3Extra phone18577Power on1bit0:Shutdown; 1: Power on
18578Fault1bit0:fault-free; 1: Faulty
18579Online status1bit0:offline; 1: online
185801bitreserve
185811bitreserve
185821bitreserve
185831bitreserve
185841bitreserve
18585-18704reserve
Command typeInternal addressregister addressvariable namedata lengthmeaningRemark
Read input register
0x04
0Number in machine30001Indoor unit type2Bytes1: Ducted Air Conditioner; 2: fresh air ventilator; 3: hydraulic module; 4, Humidifier
30002Operation Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-reserve; 6-Forced Cooling; 7-defrost; 10-self-cleaning; 11-Dehumidification and reheating; 12-Automatic dehumidificationSome models only have partial modes
30003Wind speed2BytesInternal fan speed
30004set temperature2Bytes (Actual set temperature*2) +50, The actual set temperature range is[16,30]
30005Indoor ambient temperature2Bytes (Actual temperature value*2) +50
30006Indoor environmental humidity2BytesActual humidity valueSome models are not available
30007T2temperature2Bytes (Actual temperature value*2) +50Some models are not available
30008T2Atemperature2Bytes (Actual temperature value*2) +50Some models are not available
30009T2Btemperature2Bytes (Actual temperature value*2) +50Some models are not available
30010T2Ctemperature2Bytes (Actual temperature value*2) +50Some models are not available
30011T2Dtemperature2Bytes (Actual temperature value*2) +50Some models are not available
30012Opening degree of indoor main expansion valve2Bytes
30013Indoor auxiliary expansion valve opening2BytesSome models are not available
30014-30128reserve
1Number in machine30129Indoor unit type2Bytes1: Ducted Air Conditioner; 2: fresh air ventilator; 3: hydraulic module; 4, Humidifier
30130Operation Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-reserve; 6-Forced Cooling; 7-defrost; 10-self-cleaning; 11-Dehumidification and reheating; 12-Automatic dehumidificationSome models only have partial modes
30131Wind speed2BytesInternal fan speed
30132set temperature2Bytes (Actual set temperature*2) +50, The actual set temperature range is[16,30]
30133Indoor ambient temperature2Bytes (Actual temperature value*2) +50
30134Indoor environmental humidity2BytesActual humidity valueSome models are not available
30135T2temperature2Bytes (Actual temperature value*2) +50Some models are not available
30136T2Atemperature2Bytes (Actual temperature value*2) +50Some models are not available
30137T2Btemperature2Bytes (Actual temperature value*2) +50Some models are not available
30138T2Ctemperature2Bytes (Actual temperature value*2) +50Some models are not available
30139T2Dtemperature2Bytes (Actual temperature value*2) +50Some models are not available
30140Opening degree of indoor main expansion valve2Bytes
30141Indoor auxiliary expansion valve opening2BytesSome models are not available
30142-30256reserve
nNumber in machinen*128+30000+1Indoor unit type2Bytes1: Ducted Air Conditioner; 2: fresh air ventilator; 3: hydraulic module; 4, Humidifier
n*128+30000+2Operation Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-reserve; 6-Forced Cooling; 7-defrost; 10-self-cleaning; 11-Dehumidification and reheating; 12-Automatic dehumidificationSome models only have partial modes
n*128+30000+3Wind speed2BytesInternal fan speed
n*128+30000+4set temperature2Bytes (Actual set temperature*2) +50, The actual set temperature range is[16,30]
n*128+30000+5Indoor ambient temperature2Bytes (Actual temperature value*2) +50
n*128+30000+6Indoor environmental humidity2BytesActual humidity valueSome models are not available
n*128+30000+7T2temperature2Bytes (Actual temperature value*2) +50Some models are not available
n*128+30000+8T2Atemperature2Bytes (Actual temperature value*2) +50Some models are not available
n*128+30000+9T2Btemperature2Bytes (Actual temperature value*2) +50Some models are not available
n*128+30000+10T2Ctemperature2Bytes (Actual temperature value*2) +50Some models are not available
n*128+30000+11T2Dtemperature2Bytes (Actual temperature value*2) +50Some models are not available
n*128+30000+12Opening degree of indoor main expansion valve2Bytes
n*128+30000+13Indoor auxiliary expansion valve opening2BytesSome models are not available
n*128+30000+14-n*128+30000+128reserve
63Number in machine38065Indoor unit type2Bytes1: Ducted Air Conditioner; 2: fresh air ventilator; 3: hydraulic module; 4, Humidifier
38066Operation Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-reserve; 6-Forced Cooling; 7-defrost; 10-self-cleaning; 11-Dehumidification and reheating; 12-Automatic dehumidificationSome models only have partial modes
38067Wind speed2BytesInternal fan speed
38068set temperature2Bytes (Actual set temperature*2) +50, The actual set temperature range is[16,30]
38069Indoor ambient temperature2Bytes (Actual temperature value*2) +50
38070Indoor environmental humidity2BytesActual humidity valueSome models are not available
38071T2temperature2Bytes (Actual temperature value*2) +50Some models are not available
38072T2Atemperature2Bytes (Actual temperature value*2) +50Some models are not available
38073T2Btemperature2Bytes (Actual temperature value*2) +50Some models are not available
38074T2Ctemperature2Bytes (Actual temperature value*2) +50Some models are not available
38075T2Dtemperature2Bytes (Actual temperature value*2) +50Some models are not available
38076Opening degree of indoor main expansion valve2Bytes
38077Indoor auxiliary expansion valve opening2BytesSome models are not available
38078-38192reserve
input register
0x04
(note: Currently, only Unit 0 is open for external use)
0Extra phone38193Operation Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-reserve; 6-Forced Cooling; 7-defrost; 10-self-cleaning; 11-Dehumidification and reheating; 12-Automatic dehumidificationSome models only have partial modes
38194Outdoor ambient temperature2Bytes (Actual temperature value*2) +50
38195condenser temperature2Bytes (Actual temperature value*2) +50
38196exhaust gas temperature2BytesActual temperature value
38197IPMModule Temperature3BytesActual temperature valueSome models are not available
38198Temperature of refrigerant pipe2Bytes (Actual temperature value*2) +50Some models are not available
38199Spray enthalpy inlet temperature2Bytes (Actual temperature value*2) +50Some models are not available
38200Spray enthalpy outlet temperature2Bytes (Actual temperature value*2) +50Some models are not available
38201Temperature of subcooled liquid pipe2Bytes (Actual temperature value*2) +50Some models are not available
38202Return air temperature2Bytes (Actual temperature value*2) +50Some models are not available
38203voltage value2BytesAC voltageADValue
38204current value2BytescurrentADValue
38205Opening degree of main expansion valve2BytesActual opening value
38206Opening degree of auxiliary expansion valve2BytesActual opening valueSome models are not available
38207Current external centralized control version2BytesCurrent external machine centralized control version number
38208-38320reserve
1Extra phone38321Operation Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-reserve; 6-Forced Cooling; 7-defrost; 10-self-cleaning; 11-Dehumidification and reheating; 12-Automatic dehumidificationSome models only have partial modes
38322Outdoor ambient temperature2Bytes (Actual temperature value*2) +50
38323condenser temperature2Bytes (Actual temperature value*2) +50
38324exhaust gas temperature2BytesActual temperature value
38325IPMModule Temperature3BytesActual temperature valueSome models are not available
38326Temperature of refrigerant pipe2Bytes (Actual temperature value*2) +50Some models are not available
38327Spray enthalpy inlet temperature2Bytes (Actual temperature value*2) +50Some models are not available
38328Spray enthalpy outlet temperature2Bytes (Actual temperature value*2) +50Some models are not available
38329Temperature of subcooled liquid pipe2Bytes (Actual temperature value*2) +50Some models are not available
38330Return air temperature2Bytes (Actual temperature value*2) +50Some models are not available
38331voltage value2BytesAC voltageADValue
38332current value2BytescurrentADValue
38333Opening degree of main expansion valve2BytesActual opening value
38334Opening degree of auxiliary expansion valve2BytesActual opening valueSome models are not available
38335Current external centralized control version2BytesCurrent external machine centralized control version number
38336-38448reserve
nExtra phonen*128+38192+1Operation Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-reserve; 6-Forced Cooling; 7-defrost; 10-self-cleaning; 11-Dehumidification and reheating; 12-Automatic dehumidificationSome models only have partial modes
n*128+38192+2Outdoor ambient temperature2Bytes (Actual temperature value*2) +50
n*128+38192+3condenser temperature2Bytes (Actual temperature value*2) +50
n*128+38192+4exhaust gas temperature2BytesActual temperature value
n*128+38192+5IPMModule Temperature3BytesActual temperature valueSome models are not available
n*128+38192+6Temperature of refrigerant pipe2Bytes (Actual temperature value*2) +50Some models are not available
n*128+38192+7Spray enthalpy inlet temperature2Bytes (Actual temperature value*2) +50Some models are not available
n*128+38192+8Spray enthalpy outlet temperature2Bytes (Actual temperature value*2) +50Some models are not available
n*128+38192+9Temperature of subcooled liquid pipe2Bytes (Actual temperature value*2) +50Some models are not available
n*128+38192+10Return air temperature2Bytes (Actual temperature value*2) +50Some models are not available
n*128+38192+11voltage value2BytesAC voltageADValue
n*128+38192+12current value2BytescurrentADValue
n*128+38192+13Opening degree of main expansion valve2BytesActual opening value
n*128+38192+14Opening degree of auxiliary expansion valve2BytesActual opening valueSome models are not available
n*128+38192+15Current external centralized control version2BytesCurrent external machine centralized control version number
n*128+38192+16-n*128+38192+128reserve
3Extra phone38577Operation Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-reserve; 6-Forced Cooling; 7-defrost; 10-self-cleaning; 11-Dehumidification and reheating; 12-Automatic dehumidificationSome models only have partial modes
38578Outdoor ambient temperature2Bytes (Actual temperature value*2) +50
38579condenser temperature2Bytes (Actual temperature value*2) +50
38580exhaust gas temperature2BytesActual temperature value
38581IPMModule Temperature3BytesActual temperature valueSome models are not available
38582Temperature of refrigerant pipe2Bytes (Actual temperature value*2) +50Some models are not available
38583Spray enthalpy inlet temperature2Bytes (Actual temperature value*2) +50Some models are not available
38584Spray enthalpy outlet temperature2Bytes (Actual temperature value*2) +50Some models are not available
38585Temperature of subcooled liquid pipe2Bytes (Actual temperature value*2) +50Some models are not available
38586Return air temperature2Bytes (Actual temperature value*2) +50Some models are not available
38587voltage value2BytesAC voltageADValue
38588current value2BytescurrentADValue
38589Opening degree of main expansion valve2BytesActual opening value
38590Opening degree of auxiliary expansion valve2BytesActual opening valueSome models are not available
38591Current external centralized control version2BytesCurrent external machine centralized control version number
38592-38704reserve
Command typeInternal addressregister addressvariable namedata lengthmeaningRemark
Write a single register
0x06
0Number in machine40001Set on/off switch2Bytes0:Shutdown; 1: Power on
40002Set Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-Automatic; 6-Forced Cooling; 11-Dehumidification and reheating; 12-Automatic dehumidification; Other reservations
Set automatic mode, When in dehumidification mode, The set wind speed needs to be set to102-Automatic wind
Some models only have partial modes
40003Set wind speed2Bytes1~100-Infinite wind speed gear; 102-Automatic wind
40004set temperature2Bytes (Actual temperature value*2) +50
40005Timed opening time2Bytes1Representing 1 minuteSome models are not available
40006Timed shutdown time2Bytes1Representing 1 minuteSome models are not available
40007Set target humidification humidity2Bytes1~100-1%~100%Some models are not available
40008Set target dehumidification humidity2Bytes1~100-1%~100%Some models are not available
40019-40128
1Number in machine40129Set on/off switch2Bytes0:Shutdown; 1: Power on
40130Set Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-Automatic; 6-Forced Cooling; 11-Dehumidification and reheating; 12-Automatic dehumidification; Other reservations
Set automatic mode, When in dehumidification mode, The set wind speed needs to be set to102-Automatic wind
Some models only have partial modes
40131Set wind speed2Bytes1~100-Infinite wind speed gear; 102-Automatic wind
40132set temperature2Bytes (Actual temperature value*2) +50
40133Timed opening time2Bytes1Representing 1 minuteSome models are not available
40134Timed shutdown time2Bytes1Representing 1 minuteSome models are not available
40135Set target humidification humidity2Bytes1~100-1%~100%Some models are not available
40136Set target dehumidification humidity2Bytes1~100-1%~100%Some models are not available
40137-40256
nNumber in machinen*128+40000+1Set on/off switch2Bytes0:Shutdown; 1: Power on
n*128+40000+2Set Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-Automatic; 6-Forced Cooling; 11-Dehumidification and reheating; 12-Automatic dehumidification; Other reservations
Set automatic mode, When in dehumidification mode, The set wind speed needs to be set to102-Automatic wind
Some models only have partial modes
n*128+40000+3Set wind speed2Bytes1~100-Infinite wind speed gear; 102-Automatic wind
n*128+40000+4set temperature2Bytes (Actual temperature value*2) +50
n*128+40000+5Timed opening time2Bytes1Representing 1 minuteSome models are not available
n*128+40000+6Timed shutdown time2Bytes1Representing 1 minuteSome models are not available
n*128+40000+7Set target humidification humidity2Bytes1~100-1%~100%Some models are not available
n*128+40000+8Set target dehumidification humidity2Bytes1~100-1%~100%Some models are not available
n*128+40000+9-n*128+40000+128
63Number in machine408065Set on/off switch2Bytes0:Shutdown; 1: Power on
408066Set Mode2Bytes0:Shutdown; 1-refrigeration; 2-heating; 3-air supply; 4-Dehumidification; 5-Automatic; 6-Forced Cooling; 11-Dehumidification and reheating; 12-Automatic dehumidification; Other reservations
Set automatic mode, When in dehumidification mode, The set wind speed needs to be set to102-Automatic wind
Some models only have partial modes
408067Set wind speed2Bytes1~100-Infinite wind speed gear; 102-Automatic wind
408068set temperature2Bytes (Actual temperature value*2) +50
408069Timed opening time2Bytes1Representing 1 minuteSome models are not available
408070Timed shutdown time2Bytes1Representing 1 minuteSome models are not available
408071Set target humidification humidity2Bytes1~100-1%~100%Some models are not available
408072Set target dehumidification humidity2Bytes1~100-1%~100%Some models are not available
408073-408192
Put this resource to use in a real project?

Go to the Tool Center for message parsing, CRC verification and device debugging, or submit your requirements for selection and integration advice.

Engineer Membership

Turn this article into actionable debugging resources

After activation, you can use advanced message parsing, resource pack downloads, code examples, engineering cases and priority technical support, suitable for real project delivery.

Unlimited Advanced Tools
Resource & Code Packs
Complete Engineering Case Library
Priority Technical Support

Leave a Reply

Your email address will not be published. Required fields are marked *.