1. Overview
When an S7-200 SMART PLC acts as a Modbus RTU master or slave, there is a fixed mapping relationship between its internal memory areas (I, Q, AIW, V) and the standard Modbus addresses. Based on Siemens' official technical documentation, this article explains the Modbus address mapping rules of the S7-200 SMART in detail, including complete address comparison tables, configuration steps, communication examples and a troubleshooting guide.
The S7-200 SMART supports two Modbus operating modes:
- Modbus RTU Master: actively initiates communication requests to read from or control slave devices
- Modbus RTU Slave: passively responds to the master's read/write requests
2. Modbus Address Type Description
The Modbus protocol defines four data areas, each with a fixed address range and function codes:
| Modbus Address Area | Function Code | Read/Write | Data Type | Corresponding S7-200 SMART Memory Area |
|---|---|---|---|---|
| 0xxxx (Coils) | 01 (Read Coils) / 05 (Write Single Coil) / 15 (Write Multiple Coils) | Read/Write | Bit (1 bit) | Q area digital outputs |
| 1xxxx (Discrete Inputs) | 02 (Read Discrete Inputs) | Read-only | Bit (1 bit) | I area digital inputs |
| 3xxxx (Input Registers) | 04 (Read Input Registers) | Read-only | Word (16 bit) | AIW analog inputs |
| 4xxxx (Holding Registers) | 03 (Read Holding Registers) / 06 (Write Single Register) / 16 (Write Multiple Registers) | Read/Write | Word (16 bit) | V memory area (configurable) |
Important note: Modbus addresses use 1-based numbering, i.e. counting starts from 1. PLC internal addresses are usually 0-based, starting from 0.
3. S7-200 SMART Modbus Address Mapping Table
3.1 Digital Output Area (Q Area) → 0xxxx Coils
The digital output Q area is mapped to the Modbus 0xxxx coil area and supports read and write operations.
| Modbus Address | S7-200 SMART Address | Description |
|---|---|---|
| 00001 | Q0.0 | Channel 0, bit 0 |
| 00002 | Q0.1 | Channel 0, bit 1 |
| 00003 | Q0.2 | Channel 0, bit 2 |
| 00004 | Q0.3 | Channel 0, bit 3 |
| 00005 | Q0.4 | Channel 0, bit 4 |
| 00006 | Q0.5 | Channel 0, bit 5 |
| 00007 | Q0.6 | Channel 0, bit 6 |
| 00008 | Q0.7 | Channel 0, bit 7 |
| 00009 | Q1.0 | Channel 1, bit 0 |
| 00010 | Q1.1 | Channel 1, bit 1 |
| 00011 | Q1.2 | Channel 1, bit 2 |
| 00012 | Q1.3 | Channel 1, bit 3 |
| 00013 | Q1.4 | Channel 1, bit 4 |
| 00014 | Q1.5 | Channel 1, bit 5 |
| 00015 | Q1.6 | Channel 1, bit 6 |
| 00016 | Q1.7 | Channel 1, bit 7 |
| 00017 | Q2.0 | Channel 2, bit 0 |
| 00018 | Q2.1 | Channel 2, bit 1 |
| ... | ... | And so on; every 8 addresses correspond to one byte |
| 00256 | Q31.7 | Maximum address (up to 32 bytes of outputs) |
Calculation formula: Modbus address = channel number × 8 + bit number + 1
Example: to access Q2.3, Modbus address = 2×8 + 3 + 1 = 00020
Function codes:
- Read coil status: function code 01
- Write a single coil: function code 05
- Write multiple coils: function code 15 (0x0F)
Notes:
- The Q area address mapping is fixed and requires no additional configuration
- The number of Q points actually available depends on the CPU model and expansion modules
- If the corresponding Q point does not exist in hardware, the value read back is always 0
3.2 Digital Input Area (I Area) → 1xxxx Discrete Inputs
The digital input I area is mapped to the Modbus 1xxxx discrete input area and is read-only.
| Modbus Address | S7-200 SMART Address | Description |
|---|---|---|
| 10001 | I0.0 | Channel 0, bit 0 |
| 10002 | I0.1 | Channel 0, bit 1 |
| 10003 | I0.2 | Channel 0, bit 2 |
| 10004 | I0.3 | Channel 0, bit 3 |
| 10005 | I0.4 | Channel 0, bit 4 |
| 10006 | I0.5 | Channel 0, bit 5 |
| 10007 | I0.6 | Channel 0, bit 6 |
| 10008 | I0.7 | Channel 0, bit 7 |
| 10009 | I1.0 | Channel 1, bit 0 |
| 10010 | I1.1 | Channel 1, bit 1 |
| 10011 | I1.2 | Channel 1, bit 2 |
| 10012 | I1.3 | Channel 1, bit 3 |
| 10013 | I1.4 | Channel 1, bit 4 |
| 10014 | I1.5 | Channel 1, bit 5 |
| 10015 | I1.6 | Channel 1, bit 6 |
| 10016 | I1.7 | Channel 1, bit 7 |
| 10017 | I2.0 | Channel 2, bit 0 |
| 10018 | I2.1 | Channel 2, bit 1 |
| ... | ... | And so on; every 8 addresses correspond to one byte |
| 10256 | I31.7 | Maximum address (up to 32 bytes of inputs) |
Calculation formula: Modbus address = 10000 + channel number × 8 + bit number + 1
Example: to access I3.5, Modbus address = 10000 + 3×8 + 5 + 1 = 10030
Function code: use function code 02 to read discrete inputs
Notes:
- The I area address mapping is fixed and requires no additional configuration
- Discrete inputs are read-only; the master cannot write to them
- The number of I points actually available depends on the CPU model and expansion modules
3.3 Analog Input Area (AIW Area) → 3xxxx Input Registers
The analog input AIW area is mapped to the Modbus 3xxxx input register area and is read-only.
| Modbus Address | S7-200 SMART Address | Description |
|---|---|---|
| 30001 | AIW0 | 1st analog input channel |
| 30002 | AIW2 | 2nd analog input channel |
| 30003 | AIW4 | 3rd analog input channel |
| 30004 | AIW6 | 4th analog input channel |
| 30005 | AIW8 | 5th analog input channel |
| 30006 | AIW10 | 6th analog input channel |
| 30007 | AIW12 | 7th analog input channel |
| 30008 | AIW14 | 8th analog input channel |
| 30009 | AIW16 | 9th analog input channel |
| 30010 | AIW18 | 10th analog input channel |
| ... | ... | And so on, with a step of 2 |
| 30056 | AIW110 | 56th analog input channel (maximum) |
Calculation formula: Modbus address = 30000 + AIW number / 2 + 1
Example: to read AIW20, Modbus address = 30000 + 20/2 + 1 = 30011
Function code: use function code 04 to read input registers
Notes:
- AIW uses word addressing; each AIW occupies 2 bytes, so an address step of 1 corresponds to an AIW step of 2
- Input registers are read-only; the master cannot write to them
- The analog input value range is usually 0-32767 (unipolar) or -32768 to 32767 (bipolar)
- The number of AIW channels actually available depends on the number of channels of the analog module
3.4 V Memory Area → 4xxxx Holding Registers
The mapping of the V memory area is configurable, defined by two parameters of the Modbus slave instruction MBUS_INIT:
- HoldStart: the starting V address of the holding register area (e.g. &VB1000)
- MaxHold: the number of words in the holding register area (unit: word, i.e. the number of VW)
Mapping rules:
| Modbus Address | S7-200 SMART Address | Description |
|---|---|---|
| 40001 | VW[HoldStart] | 1st holding register |
| 40002 | VW[HoldStart + 2] | 2nd holding register |
| 40003 | VW[HoldStart + 4] | 3rd holding register |
| 40004 | VW[HoldStart + 6] | 4th holding register |
| ... | ... | And so on, with a step of 2 bytes |
| 400XX | VW[HoldStart + 2 × (XX - 1)] | The XXth holding register |
Complete example: if HoldStart = &VB1000 and MaxHold = 100
| Modbus Address | V Memory Address | Byte Range | Description |
|---|---|---|---|
| 40001 | VW1000 | VB1000-VB1001 | 1st holding register |
| 40002 | VW1002 | VB1002-VB1003 | 2nd holding register |
| 40003 | VW1004 | VB1004-VB1005 | 3rd holding register |
| 40004 | VW1006 | VB1006-VB1007 | 4th holding register |
| 40005 | VW1008 | VB1008-VB1009 | 5th holding register |
| ... | ... | ... | ... |
| 40100 | VW1198 | VB1198-VB1199 | 100th holding register (the last one) |
Function codes:
- Read holding registers: function code 03
- Write a single register: function code 06
- Write multiple registers: function code 16 (0x10)
Notes:
- The V memory area mapping is configurable, set through the HoldStart and MaxHold parameters of the MBUS_INIT instruction
- HoldStart must point to a VB address, e.g. &VB1000
- The unit of MaxHold is the word (VW), not the byte (VB)
- The holding register area must not conflict with V memory already used in the PLC program
- If MaxHold is set to 100, it occupies VB1000-VB1199, a total of 200 bytes
4. PLC Slave Configuration Steps
4.1 Install the Modbus Slave Instruction Library
- Open the STEP 7-Micro/WIN SMART programming software
- Locate the "Libraries" folder in the instruction tree
- If there is no Modbus Slave library, import it first: right-click "Libraries" → "Import Library" → select the Modbus Slave library file
- The library file is usually downloaded from the Siemens official website and is named "Modbus Slave"
4.2 Call MBUS_INIT to Initialize the Slave
Call the MBUS_INIT instruction in the first scan cycle (SM0.1). The parameters are described below:
| Parameter | Value Range | Description |
|---|---|---|
| Mode | 0 / 1 | 0 = disable the Modbus slave and revert to an ordinary freeport; 1 = enable the Modbus slave |
| Baud | 1200-115200 | Baud rate; common values: 9600, 19200, 38400, 115200 |
| Parity | 0 / 1 / 2 | Parity: 0 = none, 1 = odd, 2 = even |
| Port | 0 / 1 | Communication port: 0 = onboard RS485 port, 1 = RS485 port of the SB CM01 signal board |
| SlaveAddr | 1-247 | Modbus slave address; it must not be duplicated on the same bus |
| HoldStart | &VBxxx | Pointer to the starting V address of the holding register area, e.g. &VB1000 |
| MaxHold | 0-10000 | Number of words in the holding register area (unit: word); e.g. 100 means 100 VW |
| Done | BOOL | Initialization-complete flag bit |
| Error | BYTE | Error code |
4.3 Poll MBUS_SLAVE in the Main Program
The MBUS_SLAVE instruction must be called every scan cycle in the main program loop:
- This instruction handles requests sent by the Modbus master
- If it is not called, the slave cannot respond to the master
- Parameters: Done (complete flag), Error (error code)
4.4 Configure the V Memory Area Data
Store the data to be read/written in the V address area specified by HoldStart:
- Data written by the master is stored in this area
- The PLC program reads data from this area for processing
- Make sure it does not conflict with other V addresses already used in the program
5. PLC Master Configuration and Read Example
5.1 Call MBUS_CTRL to Initialize the Master
Call the MBUS_CTRL instruction in the first scan cycle (SM0.1) to initialize the Modbus master:
| Parameter | Value Range | Description |
|---|---|---|
| Mode | 0 / 1 | 0 = disable the Modbus master, 1 = enable the Modbus master |
| Baud | 1200-115200 | Baud rate; must match the slave |
| Parity | 0 / 1 / 2 | Parity; must match the slave |
| Port | 0 / 1 | Communication port: 0 = onboard RS485, 1 = signal board |
| Timeout | 1-32767 ms | Timeout for waiting for the slave response; 1000 ms is recommended |
| Done | BOOL | Initialization-complete flag bit |
| Error | BYTE | Error code |
5.2 Call MBUS_MSG to Issue Read/Write Requests
The MBUS_MSG instruction is used to issue one Modbus read/write request:
| Parameter | Value Range | Description |
|---|---|---|
| First | BOOL | First-execution pulse; the request is issued when a rising edge is detected |
| Slave | 1-247 | Slave address |
| RW | 0 / 1 | 0 = read request, 1 = write request |
| Addr | Modbus address | The Modbus address to access; e.g. 40001 means the 1st holding register |
| Count | 1-120 | Number of registers/coils to read or write |
| DataPtr | &VBxxx | Pointer to the data buffer, e.g. &VB2000 |
| Done | BOOL | Completion flag for this request |
| Error | BYTE | Error code |
5.3 Example: Reading Holding Registers
Suppose you want to read 10 holding registers (40001-40010) from the slave device at address 1:
- First: trigger with a pulse signal
- Slave: 1
- RW: 0 (read)
- Addr: 40001
- Count: 10
- DataPtr: &VB2000
After a successful read, the 20 bytes starting at VB2000 contain the data of the 10 registers.
6. FAQ and Troubleshooting Guide
6.1 No Communication Response; the Slave Does Not Reply
- Check the wiring: whether the RS485 A+ and B- are reversed — this is the most common mistake
- Check parameter consistency: the baud rate, data bits, stop bits and parity of master and slave must be exactly the same
- Check the slave address: whether SlaveAddr is correct; there must be no duplicate addresses on the bus
- Measure the bus voltage: the A line (D+) should be about 200 mV or more above the B line (D-)
- Check the termination resistor: whether 120 Ω termination resistors are fitted at both ends of the bus (needed over long distances)
- Check the Port parameter: whether the correct communication port (0 or 1) is selected
6.2 Data Cannot Be Read or the Data Is Incorrect
- Check the address format: Modbus addresses come in 1-based and 0-based forms; distinguish them carefully
- Check HoldStart: confirm that the holding register start address is set correctly
- Check MaxHold: confirm that the number of holding registers is sufficient
- Check the address range: whether the address to read lies within the range defined by MaxHold
- Check the byte order: whether the high/low word order of 32-bit data matches the master
6.3 Garbled Data or Incorrect Values
- Check the data format: confirm whether it is a 16-bit integer, 32-bit integer or floating-point number
- Check the byte order: whether Big-Endian and Little-Endian are consistent
- Check the word order: whether the high/low word order of 32-bit data is correct
- Check the scaling: whether a multiplier is needed (e.g. values in 0.1 °C units must be divided by 10)
- Check negative-number handling: negative numbers are represented in two's complement; note the difference between signed and unsigned numbers
6.4 Intermittent Communication Failures
- Check the shielded cable: whether shielded twisted-pair cable is used for the RS485 line and whether the shield is grounded at one end only
- Check the bus length: maximum 1200 m at 9600 bps, about 100 m at 115200 bps
- Check the number of slaves: one RS485 bus can carry at most 32 slaves (without a repeater)
- Check electromagnetic interference: whether the communication cable runs parallel to power cables or there is an interference source
- Check the timeout setting: whether the Timeout parameter is set too small; try increasing it appropriately
6.5 Error Code Description
| Error Code | Description | Solution |
|---|---|---|
| 0 | No error | - |
| 1 | Parity error | Check the parity setting |
| 2 | Baud rate not supported | Check the baud rate parameter |
| 3 | Timeout error | Check wiring, slave power and timeout setting |
| 4 | Slave address error | Check the SlaveAddr parameter |
| 5 | Acknowledgement not received | The slave does not respond; check wiring and parameters |
| 10 | Gateway error | Check the gateway configuration |
7. Summary
The Modbus address mapping rules of the S7-200 SMART are clear and straightforward:
- 0xxxx coil area → corresponds to the Q area digital outputs, read/write
- 1xxxx discrete input area → corresponds to the I area digital inputs, read-only
- 3xxxx input register area → corresponds to the AIW analog inputs, read-only
- 4xxxx holding register area → corresponds to the V memory area, configurable, read/write
Once you master this mapping relationship, you can quickly implement Modbus RTU communication between an S7-200 SMART and third-party devices. In practice, it is recommended to first test the communication with debugging software such as Modbus Poll, and write the PLC program only after confirming that the address mapping is correct.