I. Product Introduction
USR-N668is an industrial grade device that implements transparent data transmission between RJ45 network ports and RS232/RS485/RS422 interfaces. It is an 8-channel serial port server
8-way serial port serverlaunched by Jinan Youren Internet Technology Co., Ltd. This device is equipped with an ARM processor, which has the characteristics of low power consumption, fast speed, and high stability.
Low power consumption, fast speed, and high stabilityThe characteristics.
TCPUsers can easily complete the networking transformation of embedded devices using it, saving development time and labor costs. This series of products has been successfully applied in complex network environments such as banks, highway surveillance, large enterprise networks, video surveillance systems, and fiber to Ethernet conversion.
2, Core functional features
| Function |
Detailed Explanation |
| 2-channel Ethernet ports |
10/100Mbps adaptive, supports AUTO-MDIX cross direct connection automatic switching |
| 8-channel serial ports |
Each serial port supports RS232/RS485/RS422 three modes that can be switched |
| IP acquisition method |
DHCP/static IP two methods |
| working mode |
TCP Server, TCP Client, UDP Client, UDP Server, Httpd Client, SSL Client, a total of 6 types |
| dual socket function |
Each channel supports dual sockets, and can send data to two different servers when acting as a client |
| TCP Server connection number |
Maximum support Connect 16 clients simultaneously |
| Heartbeat Package&Registration Package |
Customize heartbeat and registration packages to ensure reliable connections and prevent dead connections |
| Modbus TCP to RTU |
Support automatic conversion from Modbus TCP protocol to Modbus RTU protocol |
| Timeout restart/reconnect |
No data timeout restart and timeout reconnection, time can be customized |
| MAC address modification |
MAC address can be modified, factory burned with globally unique MAC address |
| DNS Domain Name Resolution |
Support DNS domain name resolution, with customizable DNS server addresses |
| remote management |
Support remote monitoring and remote firmware upgrade |
| DDNS dynamic domain name |
Support DDNS dynamic domain name resolution function such as peanut shells |
| time synchronization |
Support network time synchronization+built-in RTC real-time clock |
| Planned tasks |
Users can customize timed execution of device related instructions |
| configuration method |
There are three ways to configure web pages, software settings, and AT commands |
| Virtual Serial Port |
Supporting USR-VCOM virtual serial port software |
| VPN-PPTP |
Support PPTP protocol VPN link |
| GRE Tunnel |
Supports GRE Tunnel Protocol |
| Factory Reset |
Supports both software and hardware factory reset |
III. Technical Parameters
3.1 Electrical Parameters
| Classification |
Parameter Names |
Values |
| Hardware Parameters |
Operating Voltage |
AC 85~265V, 50/60Hz |
| Power consumption |
1.6W |
| Network port specifications |
RJ45, 10/100Mbps, cross direct adaptive |
| Number of network ports |
2 channels |
| Serial port parameters |
Serial port specifications |
RJ45 |
| Number of serial ports |
8 channels x RS232/RS485/RS422 |
| Baud rate range |
300~115200 bps |
| default parameter |
None/8/1 |
| software parameters |
network protocol |
IP, TCP/UDP, ARP, ICMP, IPv4, HTTP, SSL |
| IP acquisition method |
Static IP/DHCP |
| domain name resolution |
Support, customizable DNS server address |
| Passthrough method |
TCP Server/TCP Client/UDP Server/UDP Client/Httpd Client/SSL Client |
| web cache |
10KB, Serial port cache 10KB |
3.2 Other parameters
| Parameters |
Values |
| Shell protection level |
IP30 |
| Dimensions |
482 × 185 × 45 mm (rack mounted) |
| Operating temperature |
-40 ℃~+85 ℃ |
| Storage temperature |
-40 ℃~+105 ℃ |
| Operating Humidity |
5%~95% RH (no condensation) |
| Static electricity level (EN61000-4-2) |
Level 4 |
| Pulse group level (EN61000-4-4) |
Level 4 |
| Surge level (EN61000-4-5) |
Level 3 |
| Average transmission delay |
≥50ms |
| Packaging mechanism |
50ms packaging time, 1472 byte packaging length |
IV. Hardware Introduction
4.1 DIP Switch (Serial Mode Switching)
There is a DIP switch setting window on the back of the device, which can only be seen by removing the screw with a Phillips screwdriver. There are a total of 16 dialing codes (8 serial ports x 2/channel). Once set, it will be permanently used.
Serial Port Mode Corresponding Dialing Settings
| Communication Method |
Dialing 1 (from left to right) |
Dialing 2 (from left to right) |
| RS232 |
0 (bottom) |
0 (bottom) |
| RS485 |
1 (top) |
1 (top) |
| RS422 |
1 (top) |
0 (bottom) |
Note: silk screen printing is the standard, dial up to represent 1, dial down to represent 0; Factory default is RS485 mode (11)
4.2 Serial port pin definition (RJ45 interface)
| Serial number |
Name |
Function description |
| 1 |
232_TX/422_Z/485-B1 |
232 send; 422 signal Z; 485 signal B |
| 2 |
232_SX/422_SA1 |
232 reception; 422 signal A |
| 3 |
422_Y/485A_1 |
422 signal Y; 485 signal A |
| 4 |
422-B1 |
422 signal B |
| 5 |
NC |
empty pin |
| 6 |
GND |
232 signal ground |
| 7 |
NC |
empty pin |
| 8 |
NC |
empty pin |
Note: RS232/RS485/RS422 can only work in one way at a time; Correct dial switch coordination is required; Using 8-core Ethernet cable and crystal head to make communication cable
4.3 Indicator light description
| Indicator light name |
Identification |
Color |
Status Description |
| Power Indicator |
PWR |
Red |
Always On After Power On |
| Work Indicator |
WORK |
Green |
Cycle Flashing After Startup (500ms On/500ms Off) |
| Status Indicator |
STATE |
Red |
Function Undefined (Reserved) |
| Ready indicator |
READY |
Green |
The device is working normally and always on; Unworking Long Off |
| Serial Port Send x 8 |
TXN |
Red |
Serial Port N Send Indicator, Blinking When Data is Available |
| Serial Port Receive x 8 |
RXN |
Green |
Serial Port N Receive Indicator, Blinking When Data is Available |
V. Default Parameters
| Project |
Default Values |
| Username |
admin |
| Password |
admin |
| IP Address |
192.168.0.7 |
| Subnet Mask |
255.255.255.0 |
| Default Gateway |
192.168.0.1 |
| Working Mode |
TCP Server |
| Target Port |
20001~20008 (1st~8th Road) |
| Local Port |
20001~20008 (1st~8th Road) |
| Target IP |
192.168.0.201 |
| Serial Port Baud Rate |
115200 |
| Serial port parameters |
None/8/1 |
VI. Detailed explanation of working modes
6.1 TCP client working mode
- Actively initiate connection: As a client, actively initiate a connection request to the server and establish a connection
- KeepAlive keep alive: Send a probe packet after waiting for 60 seconds for the first time to detect abnormal disconnection (formula: 60+5 * 3=75 second detection cycle)
- Applicable scenarios: Data interaction between devices and servers, the most commonly used networking communication method
- Local port recommendation: Set to 0, use a random port number to avoid being blocked
- Cross public network requirements: The server must have a public IP or domain name
6.2 TCP Server working mode
- Passive listening: Actively listening to the set local port and responding to connection requests
- Maximum number of connections: Can accept up to 16 simultaneous connections from clients (local port cannot be set to 0)
- Broadcasting mechanism: The serial port receives data and sends it to all connected clients at the same time
- Applicable scenarios: Multiple computers/phones accessing devices simultaneously in the local area network
- Cross public networkPort mapping needs to be done on the router
6.3 UDP Client Working Mode
- Connectionless transmissionNo need to establish a connection, just specify the IP and port to send data
- Directional communicationOnly communicate with the target port of the target IP
- Broadcast supportTarget: 255.255.255.255 to achieve full network segment broadcasting (firmware 4015+supports xxx.xxx.xxx.255 network segment broadcasting)
- Not supporting multicast
6.4 UDP Server Working Mode
- Do not verify the source IPAfter receiving UDP data, change the destination to the source IP/port
- Recent communicationSend data to the nearest communication IP and port
- Applicable scenariosScenario where multiple network devices communicate at high speed and do not want to use TCP
6.5 Httpd Client Working Mode
- Serial port to HTTP conversionSend request data to a specified HTTP server via serial port
- Automatically add header informationURL and header information are automatically added by 668
- Return data processingYou can choose whether to remove the header and send it to the serial port
6.6 SSL Client Working Mode
- Encrypted transmissionSupport SSL encryption on TCP connections
- Optional encryption methodNo need to manually select encryption parameters
7, Detailed Explanation of Featured Features
7.1 SocketB dual channel function
In addition to the main Socket transparent transmission, there is also a Socket B function. The data received by the serial port is sent to both SocketA and SocketB simultaneously, and vice versa. Can be used for data backup links, with the same working mechanism as SocketA.
7.2 Heartbeat Packet Function
| Parameters |
Description |
| Heartbeat Direction |
Can be sent to the network or serial port (not running simultaneously) |
| Custom Content |
Maximum 40 bytes |
| Default Interval |
30 seconds (range 1-65535 seconds) |
| Effective Mode |
TCP Client and UDP Client Modes |
7.3 Registration Packet Function
| Type |
Description |
| Connection Registration Packet |
Sent immediately after connection establishment, used to identify device source or authorize verification |
| Data Carrying Registration Packet |
Access registration packets at the forefront of data for protocol transmission |
| Full registration |
Both of the above are executed |
| MAC registration package |
Send a 6-byte MAC address when establishing a connection |
Custom registration package can be up to 40 bytes long and supports hexadecimal input
7.4 Modbus TCP to Modbus RTU
Suitable for data conversion scenarios where the serial port side uses Modbus RTU protocol and the network side uses Modbus TCP protocol. Default closed, can be opened through a webpage. Good performance in high-frequency data collection.
7.5 VPN-PTP and GRE Tunnel
- PPTPSupport MPPE/MPPE-128 encryption; PAP/CHAP/MSCHAP/MSHAPv2 authentication; The default LCP interval is 300 seconds; MTU defaults to 1500
- GRE: Set four parameters: remote address, local address, remote tunnel address, and local tunnel address
8. AT instruction configuration
8.1 Enter AT Command Mode
- Input on UART“
+++The module returns a confirmation codea"
- Enter the confirmation code on UART“
aThe module returns+OKEnter command mode
Note: Input "+++" and "a" does not echo; T1 needs to be greater than the serial port packaging interval; T2/T3 less than 300ms; T5 less than 3 seconds
8.2 Common AT Instructions
| Instruction |
Functional Description |
| AT+WANN |
Set and query IP acquisition method, IP/subnet mask/gateway parameters |
| AT+DNS |
Set and query DNS server addresses |
| AT+SOCK |
Set Socket working mode/target IP/target port |
| AT+RELD |
Restore factory settings |
| AT+ENTM |
Exit command mode and return to transparent transmission mode |
8.3 Error Code List
| error code |
Explanation |
| -1 |
Invalid command format |
| -2 |
Invalid command |
| -3 |
Invalid operator |
| -4 |
Invalid parameters |
| -5 |
Operation not permitted |
9, Method for restoring factory settings
- Hardware buttonsPress the Reload button for 5 to 15 seconds to restore the factory (not executed for less than 5 seconds or more than 15 seconds)
- set up softwareBy configuring the software's factory reset function
- AT commandsEnter AT command mode, input
AT+RELD
- Web loginClick on the factory reset button on the webpage
10, Quick Start Guide
10.1 Hardware Preparation Checklist
- USR-N668 equipment x 1
- AC220V power cord x 1
- Mother to mother serial port cable x 1
- DB9-M to RJ45 × 1
- Network cable x 2
- One computer (with built-in RS232 port or USB to 232 converter)
10.2 Connection steps
- Connect the N668 serial port to the computer through a serial cable
- Connect the 668 Ethernet port to the PC Ethernet port using a network cable
- After confirming the hardware connection is correct, connect the power adapter for power supply
- Confirm the current serial port mode (factory default RS485) through the back dial window
10.3 Network environment check
- Turn off the computer firewall and antivirus software
- Turn off unrelated network cards and only keep one local connection
- If directly connected to a PC, set the static IP and 668 in the same network segment (such as 192.168.0.201)
10.4 Default testing process
- Open the "USR-TCP232 Test. exe" debugging assistant
- Select TCP Client mode in the network area, target IP: 192.168.0.7, port: 20001
- Set the serial port to 115200, None/8/1, open the serial port
- Conduct transparent transmission test for bidirectional data transmission and reception between serial port and network
11, Data Download
Product Model:
USR-N668 V1.0.5Instruction manual document:
USR-N668_V1.0.5.pdfOfficial website:
www.usr.cn(Jinan Youren Internet of Things Technology Co., Ltd.)
http://h.usr.cnTechnical Hotline: 4000-255-652/0531-88826739
sales@usr.cn
12, Application scenarios
- Bank system network terminal access
- Networking of ETC/Toll System Serial Devices on Highways
- PLC/Instrument/Sensor Networking in Large Enterprise Networks
- Networking of serial control devices for video surveillance systems
- Complex network environment of fiber to Ethernet conversion
- Remote monitoring of serial port equipment in factory automation production line
- Intelligent building/access control/attendance system networking
- Medical equipment serial port data collection and upload