Fusheng SC Series Controller Modbus Protocol Address Table and Description

freeFree Technical Resource

This content is free to read, suitable for basic learning and search traffic.

Fusheng SC Series Controller Modbus Protocol Address Table and Description

The RS485 port of the Fusheng SC series controller complies with the ModBus RTU protocol, and its communication format is fixed as "9600 E 8 1". Its meaning is:

-  Baud rate: 9600 bps

-  Inspection position: Occasional verification

-  Data bits: 8 Position

-  Stop position: 1 Position

Note:: The baud rate of some controllers in Fusheng is adjustable. To avoid errors, Strongly recommend using silent Recognize the set value: 9600bps

Fusheng SC The series controller only supports ModBUS RTU of Number and 3 Number function code 6 Its communication format, As follows: Number function code:

- 3 Read:  Bytes N Host request

Slave address:

Function codeInitial addressData lengthInspection codeCRC Slave response

Slave address:

Function codeData lengthData contentVerification codeCRC Number function code

- 6 Write:  Bytes 1 Host request

Slave address:

Function codeRegister addressSet numerical valuesVerification codeCRC Slave response

Slave address:

Function codeRegister addressSet numerical valuesVerification codeCRC Series controller communication address table

SC Internally

Rong Controller addressAddressModBus ClassType ReadWrite/Engineering unitnumerical rangenumerical rangeBe prepared Note:
Exhaust pressure040001WordsRead only0.01MPa0~  Sensor range 
Exhaust temperature140002WordsRead only℃-50~300 
Running time240003WordsRead onlyHour0~65535 
Loading time340004WordsRead onlyHour0~65535 
Motor current440005WordsRead onlyA0~Sensors Range 
Oil and gas drum pressure 5 40006WordsRead only 0.01MPa0~  Sensor range 
Oil and gas tank temperature640007WordsRead only℃-50~300 
Operating status(1)740008WordsRead only   
load /  Uninstall7.040008.0PositionRead only 0/11=  load 0=  Uninstall
function /  Shutdown7.140008.1PositionRead only 0/11=  function 0=  Shutdown
Proximity control /  Remote control7.240008.2PositionRead only 0/11=  Remote control 0=  Proximity control
Exhaust high temperature7.340008.3PositionRead only 0/11=  call the police
Phase sequence error7.440008.4PositionRead only 0/11=  call the police
Main motor overcurrent7.540008.5bitRead only 0/11=  call the police
Air filter pressure difference alarm7.640008.6PositionRead only 0/11=  call the police
Oil fine pressure differential alarm7.740008.7PositionRead only 0/11=  call the police
Oil filter pressure difference alarm7.840008.8PositionRead only 0/11=  call the police
Fan overcurrent7.940008.9PositionRead only 0/11=  call the police
Sensor malfunction7.1040008.10PositionRead only 0/11=  call the police
Low oil pressure7.1140008.11PositionRead only 0/11=  call the police
Main motor contactor failure Obstacles7.1240008.12PositionRead only 0/11=  call the police
Fan contactor malfunction7.1340008.13PositionRead only 0/11=  call the police
Abnormal exhaust pressure7.1440008.14PositionRead only 0/11=  call the police
Long term parking 7.15 40008.15PositionRead only  0/11= Empty for a long time parking
Operating status(2)840009WordsRead only   
Serious malfunction8.040009.0PositionRead only 0/11=  Jumping off
Minor malfunction8.140009.1PositionRead only 0/11=  call the police
Electricity Source8.240009.2PositionRead only 0/11=  power supply Open
 8.340009.3PositionRead only 0/1 
 8.440009.4PositionRead only 0/1 
 8.540009.5PositionRead only 0/1 
 8.640009.6PositionRead only 0/1 
 8.740009.7PositionRead only 0/1 
 8.840009.8PositionRead only 0/1 
 8.940009.9PositionRead only 0/1 
 8.1040009.10PositionRead only 0/1 
 8.1140009.11PositionRead only 0/1 
 8.1240009.12PositionRead only 0/1 
 8.1340009.13PositionRead only 0/1 
 8.1440009.14PositionRead only 0/1 
 8.1540009.15PositionRead only 0/1 
Remote control 9 40010WordsOnly write   
Remote startup*9.040010.0PositionOnly write 0/11=Effective
Remote shutdown*9.140010.1PositionOnly write 0/11=Effective
Forced uninstallation*9.240010.2PositionOnly write 0/11=Effective
Forced loading*9.340010.3PositionOnly write 0/11=Effective
 9.440010.4PositionOnly write 0/1 
 9.540010.5PositionOnly write 0/1 
 9.640010.6PositionOnly write 0/1 
 9.740010.7PositionOnly write 0/1 
 9.840010.8PositionOnly write 0/1 
 9.940010.9PositionOnly write 0/1 
 9.1040010.10PositionJust write 0/1 
 9.1140010.11PositionOnly write 0/1 
 9.1240010.12PositionOnly write 0/1 
 9.1340010.13PositionOnly write 0/1 
 9.1440010.14PositionOnly write 0/1 
 9.1540010.15PositionOnly write 0/1 

Note:: 1.   “Remote startup”And“Remote shutdown”, “Forced loading”And“Forced uninstallation”They are interlocked, One finger Order placement“1”Time, The other one must be reset to zero.

2.  To make“Remote startup”Or“Remote shutdown”The instruction is valid, First place“1”, 2~3 Clear to zero in seconds.

Related Tags
Put this resource to use in a real project?

Go to the Tool Center for message parsing, CRC verification and device debugging, or submit your requirements for selection and integration advice.

Engineer Membership

Turn this article into actionable debugging resources

After activation, you can use advanced message parsing, resource pack downloads, code examples, engineering cases and priority technical support, suitable for real project delivery.

Unlimited Advanced Tools
Resource & Code Packs
Complete Engineering Case Library
Priority Technical Support

Leave a Reply

Your email address will not be published. Required fields are marked *.